Customization: | Available |
---|---|
Type: | Lead-Acid Batteries |
Usage: | UPS, Electric Power, Lighting |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Designed according with the IEC61056-1/2:2012 | |
Nominal Voltage | 12Volts (6 Cells per unit) |
Nominal Capacity | @25ºC |
20hr (0.25A) 3hr (1.25A) 27min Rate (5.0A) |
7.70Ah @ to 1.75V per cell@25ºC 5.25Ah @ to 1.70V per cell 3.73Ah @ to 1.60V per cell |
Weight | Approx.(2.01± 3%)kg(1.72lbs) |
Internal Resistance | Approx. 25.5mΩ full charged @25ºC |
Maximum Discharge Current | 70A(3sec) |
Operating Temperature Range | Discharge: -20ºC~60ºC; Charge: 0ºC~50ºC Storage: -20ºC~40ºC |
Float Charging Voltage | 6.75~6.90VDC/unit Average @25ºC |
Equalization and Cycle Service | 7.20~7.50VDC/unit Average @ 25ºC |
Maximum Charging Current | 2.1A |
Terminal | F1/F2 |
Self Discharge | LONGWAY batteries can be stored for more than 6 months and the Self-discharge ratio less than 3%per month at 25ºC.Please charge batteries before using. |