Customization: | Available |
---|---|
Type: | Lead-Acid Batteries |
Usage: | Bus, UPS, Electric Power, Lighting, Electric Bicycle |
Still deciding? Get samples of US$ 23/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Battery Model | Dimension | Weight | Terminal | Packaging |
4V4.5Ah | 47.5*47.5*101.5*106mm | 0.48kg | F1/F2 | 20 PCS/CTN |
Cells per Unit | 2 |
Normal Voltage | 4V |
Capacity | 4.5Ah@20Hr-rate to 1.75V per cell@25ºC |
Weight | Approx. (0.48±3%)kg(1.058lbs) |
Maximum Discharge Current | 45A(5sec) |
Internal Resistance | Approx. 22mΩ full charged @25ºC |
Operating Temperature Range | Discharge: -20ºC~60ºC Charge: 0ºC~50ºC Storage: -20ºC~60ºC |
Nominal Operating Temperature Range | 25ºC±3ºC(77ºF±5ºF) |
Float Charging Voltage | 4.5~4.6VDC/unit Average @25ºC |
Maximum Charging Current | 1.35A |
Equalization and Cycle Service | 4.8V~5.0VDC/unit Average @ 25ºC |
Self Discharge | LONGWAY Valve Regulated Lead Acid (VRLA) batteries can be stored for more than 6 months at 25ºC. Self-discharge ratio less than 3% per month at 25ºC. Please charge batteries before using. |
Terminal | F1(0.187)/F2(0.250) |
Container Material | ABS(UL94-HB) *Flammability resistance of (UL94-V0) can be available upon request |