Cells per Unit | 6 |
Normal Voltage | 12V |
Capacity | 70Ah@10Hr-rate to 1.75V per cell@25ºC |
Weight | Approx.(21.3±3%)kg (5.71lbs) |
Maximum Discharge Current | 700A(5sec) |
Internal Resistance | Approx.6mΩ full charged @25ºC |
Operating Temperature Range | Discharge: -20ºC~60ºC Charge: 0ºC~50ºC Storage: -20ºC~60ºC |
Nominal Operating Temperature Range | 25ºC±3ºC(77ºF±5ºF) |
Float Charging Voltage | 13.7~13.9VDC/unit Average @25ºC |
Maximum Charging Current | 17.5A |
Equalization and Cycle Service | 14.4V~15.0VDC/unit Average @ 25ºC |
Self Discharge | LONGWAY Valve Regulated Lead Acid (VRLA) batteries can be stored for more than 6 months at 25ºC. Self-discharge ratio less than 3% per month at 25ºC. Please charge batteries before using. |
Terminal | Terminal F20 |
Container Material | ABS(UL94-HB) *Flammability resistance of (UL94-V0) can be available upon request |